Definite purpose contactor

Advertisement

Quick Links

Definite Purpose Contactor
Type: 45.J1.,45.J2.,42.J3.,45.J4.
IEC 60947-4-1
45.J4. (1 Pole )
45.J2. (2 Pole )
42.J36.(3 Pole with Aux)
A. Technical Data
(i) Main Circuit:
These contactors are used for control of motors, Power
supplies, Heating elements, Lighting & HVAC fans &
compressors.
·
Insulation Voltage Ui : 600V AC
·
Rated operational voltage (Ue):
240V, 50/60Hz for 1 Pole & 1 Pole with shunt
240/415V, 50/60Hz for 2 Pole & 3 Pole
·
Impulse withstand voltage Uimp= 2.5kV (Overvoltage
category II).
·
Temperature : Storage -40 to + 65 °C
Service (without derating) - 5 to + 55 °C
1 Pole without shunt
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
32
45CJ40A..
25
45DJ40A..
30
40
45EJ40A..
40
50
45.J1. (1 Pole with Shunt)
42.J35. (3 Pole)
1 Pole with shunt
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
45CJ10A..
25
32
45DJ10A..
30
40
50
45EJ10A..
40
2 Pole
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
45BJ20A..
20
32
45DJ20A..
30
40
50
45EJ20A..
40
Table 1.1
·
Switching frequency in Make/Break operation:
180 operating cycles/hour for all the ratings
(ii) Aux Circuit:
Inbuilt Auxilliary Contacts
1NO + NC in case of 42.J36A
(iii) Control Circuit:
·
Control voltage is marked on the coil of the contactor.
Note:
·
The voltage is to be maintained within allowable
limits .
·
Operation on under voltage conditions to the coil may
cause damage to the coil/contactor.
·
Maximum back-up fuse rating for control circuit= 10A
(iv) Internal connection diagram:
Connection Details
45.J1.
45.J4.
(1 Pole with Shunt)
(1 Pole without shunt)
42.J35.
(3 Pole)
Fig.1
3 Pole
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
42BJ3.A..
20
32
35
42CJ3.A..
25
42DJ3.A..
30
40
42EJ3.A..
40
50
Auxilliary Contact Rating:
Ie AC-15= 2.4A at 415V
Ie DC- 13= 0.28A at 220V
45.J2.
(2 Pole)
42.J36.
(3 Pole with Aux contact block)

Advertisement

loading

Summary of Contents for Siemens 45BJ20A Series

  • Page 1 Definite Purpose Contactor Type: 45.J1.,45.J2.,42.J3.,45.J4. IEC 60947-4-1 2 Pole 3 Pole Fuse Rating for Fuse Rating for Contactor FLA (A) Contactor FLA (A) Type 1 Coordina- Type 1 Coordina- Type Type (Ie AC8a) (Ie AC8a) tion 'gG' (A) tion 'gG' (A) 42BJ3.A..
  • Page 2 PLASTICS: Segregate as per material type for recycling through consist of recyclable materials authorised dealer. Because of the long lifetime of Siemens products the disposal guidelines may be replaced by other national regulations For disposal we recommend disassembling and seperation into following materials: when taking the product out of service.

This manual is also suitable for:

45dj20a series45ej20a series42bj3 a series42cj3 a series42dj3 a series42ej3 a series