Definite Purpose Contactor
Type: 45.J1.,45.J2.,42.J3.,45.J4.
IEC 60947-4-1
45.J4. (1 Pole )
45.J2. (2 Pole )
42.J36.(3 Pole with Aux)
A. Technical Data
(i) Main Circuit:
These contactors are used for control of motors, Power
supplies, Heating elements, Lighting & HVAC fans &
compressors.
·
Insulation Voltage Ui : 600V AC
·
Rated operational voltage (Ue):
240V, 50/60Hz for 1 Pole & 1 Pole with shunt
240/415V, 50/60Hz for 2 Pole & 3 Pole
·
Impulse withstand voltage Uimp= 2.5kV (Overvoltage
category II).
·
Temperature : Storage -40 to + 65 °C
Service (without derating) - 5 to + 55 °C
1 Pole without shunt
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
32
45CJ40A..
25
45DJ40A..
30
40
45EJ40A..
40
50
45.J1. (1 Pole with Shunt)
42.J35. (3 Pole)
1 Pole with shunt
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
45CJ10A..
25
32
45DJ10A..
30
40
50
45EJ10A..
40
2 Pole
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
45BJ20A..
20
32
45DJ20A..
30
40
50
45EJ20A..
40
Table 1.1
·
Switching frequency in Make/Break operation:
180 operating cycles/hour for all the ratings
(ii) Aux Circuit:
Inbuilt Auxilliary Contacts
1NO + NC in case of 42.J36A
(iii) Control Circuit:
·
Control voltage is marked on the coil of the contactor.
Note:
·
The voltage is to be maintained within allowable
limits .
·
Operation on under voltage conditions to the coil may
cause damage to the coil/contactor.
·
Maximum back-up fuse rating for control circuit= 10A
(iv) Internal connection diagram:
Connection Details
45.J1.
45.J4.
(1 Pole with Shunt)
(1 Pole without shunt)
42.J35.
(3 Pole)
Fig.1
3 Pole
Fuse Rating for
Contactor
FLA (A)
Type 1 Coordina-
Type
(Ie AC8a)
tion 'gG' (A)
42BJ3.A..
20
32
35
42CJ3.A..
25
42DJ3.A..
30
40
42EJ3.A..
40
50
Auxilliary Contact Rating:
Ie AC-15= 2.4A at 415V
Ie DC- 13= 0.28A at 220V